Loop-through – the loop continues through the adapter
With the loop-through variant, the AION420 passes the 4–20 mA current loop on – for example to the existing PLC or display. In parallel, the reading goes to the platform over radio.
At a glance
- Signal path
- Sensor → AION420 → controller
- Radio
- Parallel to the loop
- Existing evaluation
- Stays unchanged
SensorAION420SPS / Anzeige
+ Funk parallel
Important: never leave the loop output open
If you buy the loop-through variant but do not pass the 4–20 mA loop on, the loop output must be tied to GND – otherwise no correct measurement is possible.
The existing system stays in charge
PLC, display or control loop keep working as before – the radio data is added on top.
Monitoring without rebuilding
No intervention in the automation, no reprogramming of the controller.
How to proceed
- 1.Check whether the loop should continue to the controller
- 2.Yes: wire the loop output to the evaluation per the terminal diagram
- 3.No: tie the loop output to GND – never leave it open
- 4.Check the reading via BLE and compare it with the display